The SRX3 AC Current Data Logger combines precision measurement with practical field usability. Built for professional energy auditors, HVAC specialists, and electrical engineers, it provides a clear picture of how electrical loads behave over time — from branch circuits to high-capacity three-phase systems.
Unlike simple run-time counters that only track when equipment is on, the SRX3 shows how hard it’s working. Paired with ACR’s clamp-on current probes (available from 10 A to 1000 A), users can safely measure current without disconnecting wires or shutting down power. Each probe translates live AC current into precise data the logger records with 16-bit resolution, capturing subtle variations in load that reveal inefficiencies, imbalance, or cycling issues.
Each SRX3 supports up to seven analog inputs, allowing simultaneous monitoring of three-phase current plus auxiliary signals such as temperature, pressure, or voltage. Configurable equations in TRX Basic or TRX Pro software let users easily scale readings to engineering units and generate ready-to-share reports in CSV, XLS, or PDF format.
A rugged enclosure, wide operating range (–40 °C to +85 °C), and battery life of up to ten years make the SRX3 equally at home in mechanical rooms, plant floors, and field audit kits.
| Alarm Connector | Critical and Warning connections Maximum 15V Maximum 350mA |
| Battery | 3.6V Lithium Typical battery life: 10 years under normal operating conditions @ 25°C |
| Channel 0 - Internal Temp | Resolution: 0.01°C Range: -40°C - 85°C Accuracy: ± 0.3°C (0C to 70C) Accuracy: ± 1°C (-40C to 85C) |
| Channels 1 to 7 - DC Voltage | Input Impedance: ~ 1 Megohm Resolution: 16-bit Range: 0 – 5V DC Accuracy: ± 0.5% Full Scale |
| Clock Accuracy | ± 1 seconds per day |
| LED Status & Alarm Lights | High & Low thresholds per channel Latch / Self-reset |
| Memory Size | 1 Million Readings |
| Operating Limits | -40°C to 85°C (-40°F to 185°F) 0 to 95% RH non-condensing |
| Sample Rates | 10s to 24 hours (normal mode) 50 ms to 10 s (powered fast mode) |
| Sampling Methods | Continuous (first-in-first-out) / Stop when full Immediate start / Delayed start - up to 2 months Spot / Averaged Readings |
| Size | 111 mm (4 3/8") x 74mm (2 15/16") x 27 mm (1 1/16") |
| Status Indicator | Flash rate: 10 seconds Green: logging Blue: delayed start Yellow: alarm warning Red: critical alarm Magenta: memory full |
| Weight | 140g (5 oz) |
| Warranty | 3 Years |
ACR software tools are intuitive and flexible, allowing you to easily configure ACR data loggers to collect the data you need. Once downloaded, your data is displayed in presentation-quality graphs and can be converted into popular formats for use with spreadsheet programs, document editors, and other third-party applications.
Data loggers are often used in highly regulated environments such as food and pharmaceutical production and storage where strict safety regulations apply. Regulatory agencies generally require proof of calibration.
ACR calibrations are performed using reference standards that have been calibrated and are traceable to the US National Institute of Standards & Technology (NIST). This ensures that all ACR data loggers meet, and perform to, their published specifications, allowing you to be confident that they will assist you in achieving your compliance requirements.
Calibration certificates are provided with every calibration we perform. ACR Systems is an ISO 9001:2015 registered company and calibration records are kept as part of our quality system and can be made available for customer audits.